Water Supply PID Control Application

 1.Inverter will display motor speed,setting pressure and feedback pressure.

Setting:

1.  b9-02 LED Running parameter display 1set to C01F

2.  b9-03 LED Running parameter display 2set to 0801 

3.  b9-05 motor speed display coefficient4 poles motor set to 0.3000that is 1500rpm),2 poles motor set to 0.6000that is 3000rpm.

Set this parameter formulaSetting value= motor rated RPM/500*0.1 

4.  b9-06 motor speed display decimal point digitset to 1.

5.  After setting, press button to display following parameters: Setting frequency---DC Bus Voltage—Output voltage---Output current---Motor speed RPM---Setting pressure---Feedback pressure---Inverter temperature.

Above parameters are valid when b0-03=8 ,PID control valid.
2.Inverter PID control wiring:

3. the corresponding parameter setting:

Code

Function

Setting value

Remark

 

b0-02

Command source

1

0.keypad1.by terminal

 

b0-03

Frequency select

8

PID control

 

b2-24

Dormancy frequency

25HZ

Before set dormancy frequency, firstly set awaken frequency b2-26, and then to set dormancy frequency b2-24.

 

b2-25

Dormancy delay-time

5.0S

 

b2-26

Awaken frequency

35HZ

 

b2-27

Awaken delay time

3.0s

 

b5-20

AI2 Min value

2.00

Used for 4mA20mA

 

b5-22

AI2 second value

4.00

 

b5-24

AI2 third value

6.00

 

b5-26

AI2 fourth value

8.00

 

C0-01

Setting value

Formula=target pressure/meter range=0.2/2.5=0.08set to 8%

Setting according to requirement

 

C0-03

Feedback signal

1

Control board jumper J5 change toIinverter will accept 4~20mA signal.

 

C0-05

Sensor meter range

 

Setting according to sensor nameplate1.0MP is 10001.6MP is 16002.5MP is 2500

 

C0-25

PID feedback signal lost detection value

 

This parameter is used for protecting inverter when water dry or inverter alarm.

 

C0-26

PID feedback signal lost detection time

 

 

C0-27

PID stop operation

1

Set dormancy function,  this parameter need to set 1, otherwise dormancy function  is not working.

 

The following is sensor photo: